GUIDANCE NOTE - OHSU G24 (2000)
(Mae'r tudalennau hyn yn Saesneg yn unig ar hyn o bryd)
SAFE WORK IN CONFINED SPACES
Introduction
This guidance has been produced from the Health and Safety Executive publication 'Safe Work in Confined Spaces' and aims to give simple and practical guidance to meet the requirements of the Confined Spaces Regulations 1997.
Background
On average, work in confined spaces kills 15 people every year in the UK across a wide range of industries, from those involving complex plant through to simple storage vessels. In addition, a number of people are seriously injured. Those killed or injured include not only people working in the confined space but those who try to rescue them without proper training and equipment.
What is a confined space?
A confined space can be any space of an enclosed nature where there is a risk of death or serious injury from hazardous substances or dangerous conditions (eg lack of oxygen). Some confined spaces are fairly easy to identify, eg enclosures with limited openings, for example:
- Storage tanks.
- Silos.
- Reaction vessels.
- Enclosed drains.
- Sewers.
Others may be less obvious, but can be equally dangerous, for example:
- Open-topped chambers.
- Vats.
- Combustion chambers in furnaces etc.
- Ductwork.
- Unventilated or poorly ventilated rooms.
It is not possible to provide a comprehensive list of confined spaces. Some places may become confined spaces when work is carried out, or during their construction, fabrication or subsequent modification.
At the University
The University only has a limited number of 'confined spaces' as defined by the Confined Space Regulations: seawater tanks and attentuation tanks. All work within these areas is controlled by Property and Campus Services (PACS).
All Colleges and Departments are reminded that work within or on the fabric of a building or its services must be carried out by, or be under the control of PACS. Only PACS may issue a Permit To Work for entry into confined spaces within buildings or services following receipt of a suitable and sufficient risk assessment and safe system of work.
What are the dangers from a confined space?
Dangers can arise in confined spaces because of:
| A lack of oxygen |
|
| Poisonous gas, fume or vapour |
|
Some of the above conditions may already be present in the confined space. However, some may arise through the work being carried out, or because of ineffective isolation of plant nearby, eg leakage from a pipe connected to the confined space. The enclosure and working space may increase other dangers arising through the work being carried out, for example:
- Machinery used may require special precautions, such as provision of dust extraction for a portable grinder, or special precautions against electric shock.
- Gas, fume or vapour can arise from welding, or by use of volatile and often flammable solvents, adhesives etc.
- If access to the space is through a restricted entrance, eg manhole, escape or rescue in an emergency will be more difficult (see Emergency Procedures).
What the law says
You must carry out a suitable and sufficient assessment of the risks for all work activities to decide what control measures are necessary (The Management of Health and Safety at Work Regulations, Regulation 3). For work in confined spaces this means identifying the hazards present, assessing the risks and determining what precautions to take. In most cases the assessment will include consideration of:
- The task.
- The working environment.
- Working materials and tools.
- The suitability of those carrying out the task.
- Arrangements for emergency rescue.
The University's Risk Assessments guidance , will help you further. You may need to appoint competent people to help manage the risks and ensure employees are adequately trained and instructed (The Management of Health and Safety at Work Regulations, Regulation 6). Of course, you may be the best person to do this, however, you may need to train someone else or engage the services of a competent person for additional help.
If your assessment identifies risks of serious injury from work in confined spaces, such as the dangers highlighted above, the Confined Spaces Regulations 1997 apply. These regulations contain the following key duties:
- Avoid entry to confined spaces, eg by doing the work from outside.
- If entry to a confined space is unavoidable, follow a safe system of work.
- Put in place adequate emergency arrangements before the work starts.
These duties, and what you need to do, are further described in this Guidance Note.
Avoid Entering Confined Spaces
Check if the work can be done another way so entry or work in confined spaces is avoided. Better work-planning or a different approach can reduce the need for confined space working.
Ask yourself if the intended work is really necessary, or could you:
- Modify the confined space itself so that entry is not necessary.
- Have the work done from outside, for example:
- Clear silo blockages with remotely operated rotating flail devices, vibrators or air purgers.
- Inspection, sampling and cleaning operations undertaken from outside the space using appropriate equipment and tools.
- Remote cameras for internal vessel inspection.
Safe Systems of Work
If you cannot avoid entry into a confined space make sure you have a safe system for working inside the space.
Use the results of your risk assessment to help identify the necessary precautions to reduce the risk of injury. These will depend on the nature of the confined space, the associated risk and the work involved.
Make sure that the safe system of work, including the precautions identified, is developed and put into practice. Everyone involved will need to be properly trained and instructed to make sure they know what to do and how to do it safely.
The following checklist is not intended to be exhaustive but includes many of the essential elements to help prepare a safe system of work.
Appointment of a Supervisor
Supervisors should be given responsibility to ensure that the necessary precautions are taken, to check safety at each stage and may need to remain present while work is underway.
Are Persons Suitable for the Work?
Do they have sufficient experience of the type of work to be carried out, and what training have they received? Where risk assessment highlights exceptional constraints as a result of the physical layout, are individuals of suitable build? The competent person may need to consider other factors, eg concerning claustrophobia or fitness to wear breathing apparatus, and medical advice on an individual's suitability may be needed.
Isolation
Mechanical and electrical isolation of equipment is essential if it could otherwise operate, or be operated, inadvertently. If gas, fume or vapour could enter the confined space, physical isolation of
pipework etc needs to be made. In all cases a check should be made to ensure isolation is effective.
Cleaning Pre-entry
This may be necessary to ensure fumes do not develop from residues etc while the work is being done.
Check the Size of the Entrance
Is it big enough to allow workers wearing all the necessary equipment to climb in and out easily, and provide ready access and egress in an emergency? For example, the size of the opening may mean choosing air-line breathing apparatus in place of self-contained equipment which is more bulky and therefore likely to restrict ready passage.
Provision of Ventilation
You may be able to increase the number of openings and therefore improve ventilation. Mechanical ventilation may be necessary to ensure an adequate supply of fresh air. This is essential where portable
gas cylinders and diesel-fuelled equipment are used inside the space because of the dangers from build-up of engine exhaust. Warning: carbon monoxide in the exhaust from petrol-fuelled engines is so
dangerous that use of such equipment in confined spaces should never be allowed.
Testing the Air
This may be necessary to check that it is free from both toxic and flammable vapours and that it is fit to breathe. Testing should be carried out by a competent person using a suitable gas detector which
is correctly calibrated. Where the risk assessment indicates that conditions may change, or as a further precaution, continuous monitoring of the air may be necessary.
Provision of Special Tools and Lighting
Non-sparking tools and specially protected lighting are essential where flammable or potentially explosive atmospheres are likely. In certain confined spaces (eg inside metal tanks) suitable precautions
to prevent electric shock include use of extra low voltage equipment (typically less than 25 V) and, where necessary, residual current devices.
Provision of Breathing Apparatus
This is essential if the air inside the space cannot be made fit to breathe because of gas, fume or vapour presence, or lack of oxygen. Never try to 'sweeten' the air in a confined space with oxygen as
this can greatly increase the risk of a fire or explosion.
Preparation of Emergency Arrangements
This will need to cover the necessary equipment, training and practice drills.
Provision of Rescue Harnesses
Lifelines attached to harnesses should run back to a point outside the confined space.
Communications
An adequate communications system is needed to enable communication between people inside and outside the confined space and to summon help in an emergency.
Check how Alarm Raised
Is it necessary to station someone outside to keep watch and to communicate with anyone inside, raise the alarm quickly in an emergency, and take charge of the rescue procedures?
Permit-to-Work (see 'At the University' above for confined space work at the University)
A permit-to-work may be required before persons are allowed to enter a confined space. This process is to ensure a formal check is undertaken to confirm all the elements of a safe system of work and a suitable means of communication (between site management, supervisors, and those carrying out the work) is in place before anyone enters or works in the confined space . Essential features of a Permit-to-Work are:
- Clear identification of who may authorise particular jobs (and any limits to their authority) and who is responsible for specifying controls (eg isolation, air testing, emergency arrangements etc).
- Provision for ensuring contractors engaged to carry out work are included.
- Training and instruction in the issue of permits.
- Monitoring and auditing to ensure that the system works as intended.
EMERGENCY PROCEDURES
When things go wrong, people may be exposed to serious and immediate danger. Effective arrangements for raising the alarm and carrying out rescue operations in an emergency are essential. Contingency Plans will depend on the nature of the confined space, the risks identified and consequently the likely nature of an emergency rescue.
Emergency arrangements will depend on the risks. You should consider:
- Communications: How can an emergency be communicated from inside the confined space to people outside so rescue procedures can start? Don't forget night and shift work, weekends and times when the premises are closed, eg holidays. Also, consider what might happen and how the alarm can be raised.
- Rescue and Resuscitation Equipment: Provision of suitable rescue and resuscitation equipment will depend on the likely emergencies identified. Where such equipment is provided for use by rescuers, training in correct operation is essential.
- Capabilities of Rescuers: There need to be properly trained people, sufficiently fit to carry out their task, ready at hand, and capable of using any equipment provided for rescue, eg breathing apparatus, lifelines and fire-fighting equipment. Rescuers also need to be protected against the cause of the emergency.
- Shut Down: It may be necessary to shut down adjacent plant before attempting emergency rescue.
- First-aid: Trained first aiders need to be available to make proper use of any necessary first-aid equipment provided.
- Local Emergency Services: How are the local emergency services (eg, fire brigade) made aware of an incident? What information about the particular dangers in the confined space is given on arrival?
Relevant Law
- The Confined Spaces Regulations 1997.
- The Management of Health and Safety at Work Regulations 1999.
- The Control of Substances Hazardous to Health Regulations 2002.
- The Personal Protective Equipment at Work Regulations 2002.
- The Provision and Use of Work Equipment Regulations 1998.
- Electricity at Work Regulations 1989.
- Workplace (Health, Safety and Welfare) Regulations 1992.
Some of the above law is relevant because of the nature of the work to be carried out inside a confined space, eg where there are risks from machinery, electricity or from hazardous substances.